1
Doc Info
2
Compressor System
3
Leak Survey
4
Rates & Costs
5
Results & Export
01 Document Information
02 Compressor System
ℹ CFM per BHP depends on compressor type and pressure (e.g. 5.43 for rotary screw at ~110 psi, 4.2 for reciprocating). HP and Pressure are used in the report narrative only.
-
03 Leak Survey Results
-
04 Utility Rates & Implementation Costs
Utility Rates
ℹ Default CF = 0.77 per Focus on Energy TRM. Set to 1.0 if demand is always on-peak.
Implementation Costs
05 Live Results
Enter survey data
results update automatically
📄 Generate Word Report

Generates a complete .docx following the IAC compressed air leak assessment template - equations, summary box, system description, implementation cost.

∑ Formula Reference
Q_total = N × q_avg
P_lost = (q / BHP) × 0.746 × N × RF × LF / η
AES = P_lost × H
DR = (AES / H) × 12 × CF
ACS = AES × RE + DR × RD
PBP = IC / ACS
q = avg CFM per leak · BHP = CFM/HP of compressor
RF = running factor · LF = loading factor · η = efficiency
IC = parts + labor hours × labor rate