1
Doc Info
2
Surfaces
3
Insulation
4
Rates & Cost
5
Results & Export
01 Document Information
02 Uninsulated Surface Inventory
Add each uninsulated surface. Use one row per distinct surface, pipe, or equipment section.
Label Area A
(ft²)
Surface
Temp Ts (°F)
Ambient
Temp Tenv (°F)
Hours H
(hr/yr)
Run
Factor RF (%)
h
(Btu/ft²·hr·°F)
Qu
(MMBtu)
Σ Qu -
Quick-add presets:
Steam pipe (250°F) Boiler shell (200°F) Oven surface (300°F) Furnace shell (360°F) Hot water pipe (150°F) Tank surface (180°F)
03 Insulation Properties
Rs = 1/h = 0.7143 hr·ft²·°F/Btu (surface resistance, fixed)
Fiberglass 1" Fiberglass 1.5" Fiberglass 2" Polyiso 1" Polyiso 1.5" Mineral wool 2"
04 Energy Type, Rates & Implementation Cost
Implementation Cost
IC = -
IC = Area × $/ft² + Labor hours × $/hr
05 Live Results
Add surfaces and
fill inputs to see results
📄 Generate Word Report

Generates a complete .docx following the IAC insulation template - Qu, Qi, AES, ACS, implementation cost with payback.

∑ Formula Reference
Qu = h × A × ΔT × H × RF / 10⁶
Qi = A × ΔT × H × RF / (Rs+Ri) / 10⁶
AES = (Qu − Qi) / η
ACS = AES × RGa (gas)
IC = A × $/ft² + Labor hrs × $/hr
PBP = IC / ACS
h = 1.4 Btu/ft²·hr·°F (default bare steel).
Rs = 1/h = 0.7143. Ri from insulation table.
η = heating source efficiency.