1
Doc Info
2
Doors
3
Infiltration
4
Thermal
5
Rates & Costs
01 Document Information
02 Door Type & Configuration
🪟
Strip Curtain
70% infiltration reduction
💨
Air Curtain
80% infiltration reduction
⚡
High-Speed Door
Based on speed ratio
🔥 Heating Only
❄️ Cooling Only
🔥❄️ Both
# Door / Location W (ft) H (ft) Qty
+ Door + Loading Dock 12×14 + Overhead 18×15 + Cooler Door 4×7 + Personnel 3.5×7
-
03 Infiltration & Operating Parameters
04 Thermal Parameters
🔥 Heating Season
05 Utility Rates & Implementation Cost
Utility Rates
Implementation Cost
↻ Live Results
Infiltration
Door Area -
Flow Rate (Qi) -
Reduction Factor -
Heating Savings
Heat Loss (QW) -
Gas Savings -
Cooling Savings
Cooling Load (QCs) -
Elec Savings (net) -
Demand Reduction -
Economics
Annual Cost Savings -
Implementation Cost -
Payback Period
-
03 yr7 yr10+ yr
📄 Generate Word Report

Generates a complete .docx following the IAC AR template - infiltration equations, seasonal savings, IC & payback.

Formula Reference
Qi = A × O% × V × 88
Infiltration flow rate (cfm)
QW = 1.10 × Qi × ΔTh × Hh
Heating season heat loss (Btu/yr)
AESG = QW × EF / (ηh × 10⁶)
Gas savings (MMBtu/yr)
QCs = 1.10 × Qi × ΔTc × Hc
Cooling season sensible load (Btu/yr)
AESE = QCs × EF / (EER × 1000)
Electric savings (kWh/yr)
EF (strip) = 70% | (AC) = 80%
EF (high-speed) = 1 − vslow/vfast